Contact Us

Products Information
- Integrated design,small size,expedient installation and simple maintenace. Products are applicable for interface LPZ0B-LPZ1(lightning protection zones)
- The core parts are metal oxide vanistor and Gas Discharge Tube(GDT) With high discharge capacity&reliable quality
- Low residual voltage, fast response time
- Thermo Dynamic control disconnector can automatically cutoff the circuit to protect from fire accident entirely. The flameproof & explosion-proof functions are especially applied in the fire protection situations
- Fit for TT and TN system protection against common-mode or differential-mode interferences
- Rarefied craftwork, Can work permanently in adverse conditions, such as acid, alkali, saltspray and humidity, ect.

| KB-EPT31/ 120-250 |
KB-EPT31/ 120-275 |
KB-EPT31/ 120-320 |
KB-EPT31/ 120-385 |
KB-EPT31/ 120-420 |
|
| Max.continuous operating volage Uc (V) | 250V | 275V | 320V | 385V | 420V |
| Voltage protection level L-N(20kA)Up | ≤1.5kV | ≤1.8kV | ≤2.0kV | ≤2.2kV | ≤2.5kV |
| Power network system | TT/TN | ||||
| Nominal discharge current In(8/20 μs) | 40kA | ||||
| Max. discharge current Imax(8/20 μs) | 80kA | ||||
| Operating temperature range | -40°c~+85°c | ||||
| Relative humidity(at room temperature) | ≤95% | ||||
| Protection Mode | Single-phase Full Protected Mode | ||||
| Test standards | IEC 61643-1:1998 | ||||
| Connecting cable section area | 16mm²(in side of power supply)25mm²(in side of protecting earth line) | ||||
| Degrees of protection | IP21 | ||||